  Technical / Design guidelines / Long length sheets
 
Kalzip
 

Long length Kalzip

Kalzip sheets are commonly used in long lengths (with continuous lengths in excess of 150 metres being achieved) therefore the understanding and control of thermal movement is a prime
consideration.

Thermal movement
The colour and finish of a roof will also play an important role in determining the anticipated thermal movement. As a rule of thumb the following thermal movement rates are adopted for aluminium.

 
     
Finish Approx. temperature attained Movement per metre length (mm)
 

Stucco/mill

40° - 50°C

1.0

Light colour

40° - 50°C

1.0

Dark colour

70° - 80°C

1.5

It is recommended that on roof areas with sheet lengths exceeding 40 metres the Kalzip E clip is used. These allow for a more efficient accommodation of thermal movement which is particularly relevant when designing the structure, sub-structure and fasteners to accommodate long lengths of standing seam sheets; potentially allowing thinner structural material and fewer fasteners to be used.

If you would like more information on using long length Kalzip sheets, please contact the Kalzip Technical Department.